Freezer will not freeze water, gets cold enough to freeze the top layer of water, but not all the way through. I've checked and topped off the refrigerant and have also cleaned the coils in the back. Any suggestions will be greatly appreciated.

Research, Knowledge and Information :


www.thedomains.com


27f.london 27g.london 27h.london 27i.london 27j.london 27k.london 27l.london 27m.london 27n.london 27o.london 27p.london 27q.london 27r.london 27s.london 27t.london ...
Read More At : www.thedomains.com...

Suggested Questions And Answer :


TRUE under counter FREEZER TU2-27F


Are both evaporator fan and condensor fan running?You stated that you topped off the charge.Assuming the charge is ok, the next thing to check would be the expansion valve.May not be metering the freon properly.A faulty expansion valve can trick you into thinking the unit is undercharged.It may be partially open and starving the evaporator.(Not freezing the water totally)You should have a even coating of frost on the evaporator coil when running.Hope this helps,let me know if i can assist you any further.
Read More At : 12 cu. ft. / 340 liter Commercial Freezer T-12F...

In defrost mode all the time - True 6.5 cu. ft. / 184 liter Commercial Freezer TUC-27F


It sounds to me like the defrost timer has burned out youl need to get a service man to conferm but strat there
Read More At : 6.5 cu. ft. / 184 liter Commercial Freezer TUC-27F...

True Freezer Running Too Cold


Thermostat is stuck closed, if not compressor relay is stuck closed, if not then the defrost timer is stuck closed. test the components in that order.
Read More At : 12 cu. ft. / 340 liter Commercial Freezer T-12F...

Takes weeks to freeze


If you freezer has a defrost timer it should have done the defrost on its own. Only the very old freezers had to be defrosted manually. If it continues to stop cooling or you already haven't had the timer replaced or the defrost elements checked let me know.
Read More At : 12 cu. ft. / 340 liter Commercial Freezer T-12F...

I have a true freezer m/# gdm-49f s/# 5140302 ... this unit is set at -17* it runs fine when it gets to the set point turn off of course by it doesn't come back on until it reaches 0* .... I like to know if that is normal? .. no product is damage


Well most t stats have a differential of 5 to 7 but almost never more than ten deg so that the compressor wont short cycle .something you can check .some t stats you can adjust the differential on check if yours has that adjustment screw on the side or back of T stat if you need more help or parts e mail me at [email protected]
Read More At : 49 cu. ft. / 1388 liter Commercial Freezer GDM-49F-RC...

True Fridge Running Hard


I would try this: unplug unit and use a vacuum cleaner and vacuum out the entire area. Not sure what you mean by "running really hard"? If you mean noisy, then see if you can see source after cleaning. Try this and let me know if I can be of any further help.
Read More At : 12 cu. ft. / 340 liter Commercial Freezer T-12F...

True GDM-72f freezer Fans don't start - True 72 cu. ft. / 2039 liter Commercial Freezer GDM-72F


Thermo fuse has failed on the core plate, tells the freezer its cold enough to start blowing air, you can bypass it but not recommended. hope that helps, Russ
Read More At : 72 cu. ft. / 2039 liter Commercial Freezer GDM-72F...

Tips for a great answer:

- Provide details, support with references or personal experience .
- If you need clarification, ask it in the comment box .
- It's 100% free, no registration required.
next Question || Previos Question
  • Start your question with What, Why, How, When, etc. and end with a "?"
  • Be clear and specific
  • Use proper spelling and grammar
all rights reserved to the respective owners || www.glacierfreezer.com || Terms of Use || Contact || Privacy Policy
Load time: 0.0683 seconds